CS 25J1199 Extinguishing agent containers
ED Decision 2005/006/R
(a) Each
extinguishing agent container must have a pressure relief to prevent bursting
of the container by excessive internal pressures.
(b) The
discharge end of each discharge line from a pressure relief connection must be
located so that discharge of the fire extinguishant agent would not damage the
aeroplane. The line must be located or protected to prevent clogging caused by
ice or other foreign matter.
(c) There
must be a means for each fire extinguishing agent container to indicate that
the container has discharged or that the charging pressure is below the
established minimum necessary for proper functioning.
(d) The
temperature of each container must be maintained, under intended operating
conditions, to prevent the pressure in the container from:
(1) Falling below that necessary to provide an
adequate rate of discharge; or
(2) Rising high enough to cause premature
discharge.
(e) If a
pyrotechnic capsule is used to discharge the extinguishing agent, each
container must be installed so that temperature conditions will not cause
hazardous deterioration of the pyrotechnic capsule.