AMC to
Appendix S, S25.10(c) Isolated Compartments
ED Decision 2017/015/R
(1) Cabin
Compartments
(a) Compartments
to be considered as isolated
Compartments in an aeroplane with an approved passenger capacity of
less than 20 and a cabin length of 18.29 m (60 ft) or less do not need, in any
case, to be considered as isolated. AMC 25.854 provides guidance on how to
determine the cabin length.
S25.10(c) requires that a compartment in which a fire would not be
directly or would not be quickly detected by occupants of another compartment
must meet additional criteria in order to provide confidence that a fire will
be detected. Such a compartment is described as an isolated compartment.
Any compartment that can be occupied by crew members and/or passengers
during flight (other than accessible cargo/baggage compartments) should be
considered as isolated for the purposes of showing compliance to S25.10(c) if
it cannot be assured that fire/smoke in the compartment will be quickly
detected by occupants of other occupied compartments of the aeroplane due to
rapid smoke/fumes transmission enabled by the design of the aeroplane.
The assurance that fire/smoke will be quickly detected by occupants of
other occupied compartments in the aeroplane may be provided by obvious
smoke/fumes passage features, e.g. grills/louvres in a door, or via the
aeroplane’s environmental control system air recirculation characteristics.
Substantiation of the effectiveness of such declared smoke/fumes transmission
means, via ground and/or flight tests, may be required. Detection of fire/smoke by occupants of another compartment only will
provide the required assurance if there is confidence that this other
compartment in question will be occupied, and not by sleeping persons (i.e. it
is a compartment that meets the conditions set out in paragraph (1)(b)(ii)
below). Thus, if smoke/fumes transmission is relied upon for compliance, the
occupancy conditions of the aeroplane as a whole need to be taken into
account.
(b) Isolated
compartments occupied for the majority of the flight time
S25.10(c) exempts isolated compartments (as described in paragraph (a)
above) that are occupied for the majority of the flight time from being
equipped with a smoke/fire detection system, based on the assumption that the
occupants will quickly detect the fire.
(i) However,
some categories of isolated compartments will by their nature not be eligible
for this approach, either because there is a risk that all occupants will be
sleeping (sleeping persons will not be able to detect a fire starting in the
isolated compartment), or because occupancy for the majority of the flight
time cannot be realistically assessed. Examples include, but are not limited
to, the following:
(A) bedrooms,
(i.e. rooms containing any sleeping installations intended to provide a high
level of sleeping comfort, such as beds, or berthable divans, even if they
also contain seats that can be occupied during taxiing, take-off, and landing;
however, passenger seats do not need to be considered as sleeping
installations in this context);
(B) specialised
rooms for which permanent occupation during the flight is unlikely (examples
would include smoking rooms, cinema rooms, etc.);
(C) washrooms/bathrooms,
although the intent of S25.10(c) will be met in any case, if they are
compliant with CS 25.854; however, a shower cubicle does not need to be
considered an isolated compartment;
(D) crew
rest compartments; and
(E) galley
compartments.
(ii) On the
other hand, an isolated compartment, unless meeting one of the criteria in (i)
above, will be accepted as being occupied for at least the majority of the
flight time, thus providing for smoke/fire detection by the occupants, if any
of the following conditions are met:
(A) it is
the flight crew compartment
(B) all
required cabin crew seats are located in the isolated compartment;
(C) the
isolated compartment contains a crew station that due to its specialised
purpose, is likely to be occupied for the majority of the flight time;
(D) the number of seats in the isolated compartment (including cabin attendant seats and seats in excess) approved for occupancy during taxiing, take-off, and landing is at least equal to the number indicated in the right hand column of the table below.
|
Total number of
passenger seats installed on the aeroplane approved for occupancy during
taxiing, take-off, and landing (including seats in excess) |
An isolated
compartment is accepted as being occupied for the majority of the flight
time if it contains at least the following number of seats approved for
occupancy during taxiing, take-off, and landing |
|
Up to 19 |
2 |
|
20–23 |
3 |
|
24–29 |
4 |
|
30–36 |
5 |
|
37–43 |
6 |
|
44–49 |
7 |
|
50–56 |
8 |
|
57–63 |
9 |
|
64 and above |
10 |
Note:
the ‘Up to 19’ figure is included for the case of an aeroplane with a total
cabin length in excess of 18.29 m (60 ft).
(iii) In
addition, an isolated compartment featuring no seat and no stowage (e.g. a
connecting corridor) might be accepted as being an isolated compartment
without a smoke/fire detection system, because of the low likelihood of a fire
starting in such a compartment.
(c) Minimum
requirements for compartments
For all compartments, irrespective of whether or not they are required
to have a smoke/fire detection system installed:
(i) For
accessibility and firefighting purposes, sufficient lighting in the
compartment should be provided. For compartments that could be dark during
flight, a means should be provided to enable a person entering the compartment
to readily gain visibility of the interior. Such means may be:
(A) a
conveniently located, easy to find and use lighting control for the
compartment;
(B) a
flashlight within close proximity to the entrance of the compartment; or
(C) automatic
illumination in the event the smoke/fire detection system in the compartment
(if installed) triggers.
(ii) At least
one readily accessible handheld fire extinguisher should be available for use
in each compartment. Fire extinguishers required by CS 25.851(a) may be used
for this purpose. On the other hand this may also lead to the need to install
more fire extinguishers than the minimum required by CS 25.851(a).
(iii) Portable
breathing equipment, required by CS 25.1439(a), should be located close to the
handheld fire extinguisher.
(b) Smoke/fire
detection in isolated compartments
For interiors with more than one isolated compartment, there should be
means by which flight or cabin crew can readily identify in which compartment
smoke/fire has been detected. Depending on the number of isolated compartments
and the specific layout, such means might be simply moving through the cabin
and checking each compartment (in the case that cabin crew are required to be
on board) or might need to be a visual indication outside each compartment, or
some form of annunciator panel available to an appropriate crew member. The
objective in any case is that correct identification of the location of the
smoke/fire should be possible without unnecessary delay.
If the isolated compartment incorporates a stowage compartment of a
volume greater than 0.7 m3 (25 ft3), this stowage compartment should be itself
equipped with a smoke detector, unless it can be demonstrated that smoke from
within the stowage compartment will be detected by the detector of the
isolated compartment in which the stowage compartment is located (e.g. through
grilles in the stowage door), and within the time specified in the requirement
S25.10(c).
If the isolated compartment incorporates a galley, or if smoking is to
be allowed in the isolated compartment, nuisance triggering of the smoke/fire
detection system may be minimised by a design feature that provides for
temporary system deactivation by an occupant (passenger or crew member). In
that case, full reactivation should be automatic after a time period of no
longer than 10 minutes following the last deactivation action.
The effectiveness of the smoke/fire detection system should be
demonstrated for all approved operating configurations and conditions. For smoke detection demonstration, FAA AC 25-9A, Smoke detection,
penetration, and evacuation tests and related flight manual emergency
procedures, 6 January 1994 provides acceptable means of compliance.
During testing, it should be demonstrated that no inadvertent operation
of smoke/fire detectors in any compartment would occur as a result of fire
starting in any other compartment.
An assessment of the compartment design and observations during smoke/fire detection tests will be expected in order to provide a demonstration of the effectiveness of firefighting procedures. This should also include demonstrating that the compartment is provided with sufficient access in flight to enable a crew member to effectively reach any part with the contents of a handheld fire extinguisher.