CS 25J1183 Lines, fittings and components
Available versions for ERULES-1963177438-9364
ED Decision 2005/006/R
found in: CS-25 Amdt 27 - Large Aeroplanes (Jan 2023)
Version
CS-25 Amdt 27 - La... (Jan 2023)
Section
Share
Version
Show details
Hide details
Version
CS 25J1183 Lines, fittings and components ED Decision 2005/006/R (a) Except as provided in sub-paragraph (b) of this paragraph, each line, fitting, and other component carrying flammable fluid in any area subject to APU fire conditions, and each component which conveys or contains flammable fluid in a designated fire zone must be fire resistant, except that flammable fluid tanks and supports in a designated fire zone must be fireproof or be enclosed by a fireproof shield unless damage by fire to any non-fireproof part will not cause leakage or spillage of flammable fluid. Components must be shielded or located to safeguard against the ignition of leaking flammable fluid. (b) Sub-paragraph (a) of this paragraph does not apply to: (1) Lines and fittings already approved as part of an APU, and (2) Vent and drain lines, and their fittings, whose failure will not result in, or add to, a fire hazard. (c) All components, including ducts, within a designated fire zone which, if damaged by fire could result in fire spreading to other regions of the aeroplane, must be fireproof. Those components within a designated fire zone, which could cause unintentional operation of, or inability to operate essential services or equipment, must be fireproof. [Amdt 25/1]